Sold Industrial Property (TN001202)
Address:
103 Palladium Way
Anderson County
Oak Ridge, TN 37830
Location:
Eastern Part of State/25 Miles West of Knoxville, Off Hwy. 179
Building Size:
66,736 SF
Lot Size:
21 Acres
Click here to view interactive Oak Ridge website
Attachments
Brochure
Download
Floor plan
Download
Property Description
Year Built
2000
Pad ready to more than double current facility. Expansion panels are in place in several areas. Current infrastructure is sufficient to support additional 70,000 s.f. addition.
Quality
Excellent
Office
4,709 SF
With 2,861 s.f. of offset main office space featuring stack stone exterior wall with plate glass & painted metal roof facade with skylights. Includes conference room, kitchen & break area, 3 private offices & reception area.
Dimensions
314' x 135' with offsets
Ceiling Height
Min: 9', Max: 40'
Ceiling Comments
Lab & Office:
9' - dropped acoustic ceiling tile, 18'3" clear under beam
2nd Floor Lab:
9' - dropped acoustic ceiling tile, 21'9" clear under beam
Crane Served High Bay:
40'
Central Plant/Utility Rooms:
23'4"
Column Comments
Steel "I" beam
Roof
Firestone white rubber membrane, mechanically attached over metal decking
Floors
1st Floor:
Concrete slab ranging from 6" - 18" with tile covering in lab area
2nd Floor:
Poured reinfoced concrete over metal decking supported by steel beams & steel joists
Walls
Architectural relief concrete panels with steel framing
Lighting
Fluorescent & incandescent with metal halide in unfinished areas
Loading
North wall:
1 - 12' x 12' drive in
1 - 18' x 28' drive in
South wall:
1 - 9' x 12' drive in
West wall:
1 - 12' x 12' drive in
1 - 12' x 12' 2nd story door to be accessed via fork lift
Cranes
1 - 5 ton DeShazo bridge crane with radio controls
90' x 75' - travel & span, 28' CUH
Parking
Mfg. Area:
60 paved, marked & lighted
Office Area:
9 paved, marked & lighted
Rail
No - Not available
Gas
Oak Ridge Utility District -
4" main, 2" line
Water
City - Industrial water, 4" line (no sewer costs)
Potable water, 3" line
Sewer
City - 8" force main & gravity lines flowing to a 15" line to facility treatment center
Power
City
13,400VAC, 3 phase - 5MW expandable to 7.5MW
480/277VAC, 3 phase - 208/120V, 3 phase, 5MW
Redundant capabilities with 2 transformers & 2 switchgears
2 - 2,500kVA pad mounted transformers
Distribution via conduit and cabling trays
Heat
Entire facility is climate controlled for temperature & humidity with exception of 6,700 s.f. mechanical space. Temperature control is achieved through a 4 pipe system consisting of chillers, boilers, frequency drive pumps, HVAC units & heat exchangers.
Air Conditioning
Yes - Humidity control is maintained through HVAC and steam injection.
Sprinklers
Yes - 100% predominantly wet system, Ordinary Group I - light hazard in office areas and Ordinary Group II in specific mechanical rooms/central plant
Hydrants: static pressure 90psi; residual pressure 60psi; 1186 GPM - 3 riser system: 106psi, 112psi & 90psi; flow pressure: 70psi, 60psi & 70psi respectively
Sprinkler system monitored by Simplex 4120 fire detection network
Air Line
Dual head 220 scfm Gardner-Denver compressor, 120 psi service pressure
Twin AirTek SC220 refrigerated air dyers
Lab Space
Yes - 12,237 s.f. of climate controlled space with one time pass through air.
6 - energy saving fume hood fixtures (Phoenix Hoods)
All labs are supplied with compressed air, water, DI water, oxygen, argon, nitrogen, natural gas & spare system
Equipment
- Vault - 11' x 6' class 5A Fort Knox vault meeting Chubb Class 5A Mercantile requirements
- Sound proof room in production area
- Industrial wash area
- Transformer vault with 2,000 gallon liquid sump, dry chemical fire suppression and isolated HVAC
- Chemical clean recovery room
Fiber
T1 - Dual T1 feeders with internal LANs
Special Features
The following infrastructure systems are monitored & controlled by the Johnson Controls Metasys Facility Management System. All rotating equipment has been placed on frequency drives for optimized energy efficiency. All utility systems are distributed evenly through the lab and mfg areas.
- Industrial cooling water system
- Deionized cooling water system
- Chilled water system
- Steam & hot water system
- Water treatment/Waste water system
- Cryogenic systems
- Compressed air system
Miscellaneous
- Roane County 2005 taxes estimated at $189,384. May be adjusted depending on local incentives offered.
- Simplex NT3400 access control system (badge system), full external monitoring
- Completely fenced & protected by guard shack
FOR MORE INFORMATION ON THIS FACILITY, PLEASE VISIT:
WWW.OAKRIDGELAB.COM
Last Use
Research and Development - Separation of stable (non-radioactive) isotopes
Hart Corporation
-
900 Jaymor Rd, Southampton, PA 18966
-
1-800-368-4278
-
hart@hartcorp.com
All information furnished is from sources deemed reliable, but no warranty or representation is made as to the accuracy thereof and same is submitted subject to errors, omissions, change of price, rental or other conditions, without notice. No liability of any kind is to be imposed on the broker herein.